Factors Stimulating Propagation of Legionellae in Cooling Tower Water
Our survey of cooling tower water demonstrated that the highest density of legionellae, ≥10(4) CFU/100 ml, appeared in water containing protozoa, ≥10(2) MPN/100 ml, and heterotrophic bacteria, ≥10(6) CFU/100 ml, at water temperatures between 25 and 35°C. Viable counts of legionellae were detected ev...
Na minha lista:
| Publicado no: | Appl Environ Microbiol |
|---|---|
| Principais autores: | , , , , , |
| Formato: | Artigo |
| Idioma: | Inglês |
| Publicado em: |
American Society for Microbiology (ASM)
1992
|
| Assuntos: | |
| Acesso em linha: | https://ncbi.nlm.nih.govhttps://pmc.ncbi.nlm.nih.gov/articles/PMC195609/ https://ncbi.nlm.nih.govhttps://pubmed.ncbi.nlm.nih.gov/16348704/ https://ncbi.nlm.nih.govhttps://doi.org/10.1128/aem.58.4.1394-1397.1992 |