QR Code

Factors Stimulating Propagation of Legionellae in Cooling Tower Water

Our survey of cooling tower water demonstrated that the highest density of legionellae, ≥10(4) CFU/100 ml, appeared in water containing protozoa, ≥10(2) MPN/100 ml, and heterotrophic bacteria, ≥10(6) CFU/100 ml, at water temperatures between 25 and 35°C. Viable counts of legionellae were detected ev...

Description complète

Enregistré dans:
Détails bibliographiques
Publié dans:Appl Environ Microbiol
Auteurs principaux: Yamamoto, Hiroyuki, Sugiura, Minoru, Kusunoki, Shinji, Ezaki, Takayuki, Ikedo, Masanari, Yabuuchi, Eiko
Format: Artigo
Langue:Inglês
Publié: American Society for Microbiology (ASM) 1992
Sujets:
Accès en ligne:https://ncbi.nlm.nih.govhttps://pmc.ncbi.nlm.nih.gov/articles/PMC195609/
https://ncbi.nlm.nih.govhttps://pubmed.ncbi.nlm.nih.gov/16348704/
https://ncbi.nlm.nih.govhttps://doi.org/10.1128/aem.58.4.1394-1397.1992
Tags: Ajouter un tag
Pas de tags, Soyez le premier à ajouter un tag!