Cargando...
Factors Stimulating Propagation of Legionellae in Cooling Tower Water
Our survey of cooling tower water demonstrated that the highest density of legionellae, ≥10(4) CFU/100 ml, appeared in water containing protozoa, ≥10(2) MPN/100 ml, and heterotrophic bacteria, ≥10(6) CFU/100 ml, at water temperatures between 25 and 35°C. Viable counts of legionellae were detected ev...
Gardado en:
| Main Authors: | , , , , , |
|---|---|
| Formato: | Artigo |
| Idioma: | Inglês |
| Publicado: |
1992
|
| Assuntos: | |
| Acceso en liña: | https://ncbi.nlm.nih.gov/pmc/articles/PMC195609/ https://ncbi.nlm.nih.gov/pubmed/16348704 |
| Tags: |
Engadir etiqueta