Horizontal convective boiling of R448A, R449A, and R452B within a micro-fin tube
This article presents local convective boiling measurements in a micro-fin tube for three low global warming potential refrigerants: R448A, R449A, and R452B(). An existing correlation was modified to predict multi-component mixtures, which predicted 98% of the measurements to within ±20%. The new co...