A field study of the survival of Legionella pneumophila in a hospital hot-water system.

The colonization, survival and control of Legionella pneumophila in a hospital hot-water system was examined. The organism was consistently isolated from calorifier drain-water samples at temperatures of 50 degrees C or below, despite previous chlorination of the system. When the temperature of one...