Airborne infection in a fully air-conditioned hospital. II. Transport of gaseous and airborne particulate material along ventilated passageways.

A mathematical model is described for the transport of gaseous or airborne particulate material between rooms along ventilated passageways. Experimental observations in three hospitals lead to a value of about 0.06 m.2/sec. for the effective diffusion constant in air without any systematic direction...